What is Circulation (outdoor)?

The circulation pumps are the heart of the water loop: they move the entire pool volume through filter and heat exchanger several times a day (the pool-water treatment standard turnover).

As a 24/7 base load they are one of the biggest power consumers in the facility. With variable-speed pumps (VFD) the AI matches flow to bather load instead of running flat-out — saving a large share of the pumping electricity.

Schematic (native, live)

Solar gain, night radiation, wind, pool cover as the lever:

Sun/windOutdoor poolPool cover

Overview: The Glass Pool → · Markets: pool markets →

Live —

loading

What the AI does

The AI controls pump speed to bather load (VFD) instead of full load and shifts circulation peaks into PV hours.
What the AI reads
Scenario

Monitored: continuously · flow, suction pressure and pump power

The scenario: Resistance on the suction side grows slowly. The pump keeps up by drawing more power, so nothing looks wrong — until the required turnover time is quietly no longer met.

Method proven on a live European reference aquatic center; presented anonymously.

Value calculator

Estimate from metered / design values. Zero-grid-import windows are real (metered).

Standards & norms

What the rules require — Circulation (outdoor)

Grounded in the applicable national standards for pool water treatment, plant energy performance and building energy performance. Same knowledge base as the European reference site; presented anonymously.

What do the applicable standards require regarding Filtration and circulation?

The applicable standard prescribes a maximum residence time of the pool water, depending on pool type: swimmer pools 4 h turnover, non-swimmer/paddling 1-2 h. This sets the minimum filter flow rate. For a 242 m³ lap pool at 4 h turnover that is 60.5 m³/h of filter capacity. Filter backwash once per day or above 0.5 bar differential pressure. Backwash water is warm (pool temperature − 3-5 K) and therefore a valuable heat-pump source.

Basis: the applicable national standard

What do the applicable standards require regarding Pool evaporation balance?

Evaporation from the water surface is the dominant heat loss in an indoor pool (60-80 %). Smith/Löf variant of the Carrier formula: m_evap [kg/h] = β × A [m²] × (p_w_pool − p_w_hall) [kPa]. β-coefficient per the pool energy guideline (evaporation and ventilation) Tab. 4: 0.013 unused pool (covered), 0.040 normal use, 0.080 wave/diving pool. Evaporation enthalpy at 30 °C: 0.694 kWh/kg. Pool saturation vapour pressure via the Magnus formula: 611.2 × exp(17.62 × t / (243.12 + t)) Pa.

Basis: the applicable national standard

What do the applicable standards require regarding Outdoor-pool convection and radiation?

Outdoor pools have higher convection and radiation losses. Convection: h_conv = 4 + 11 × v_wind [W/(m²·K)] with v in m/s. At 1 m/s wind: h ≈ 15 W/(m²·K). Night radiation (clear sky): ~60 W/m² over a 10 h night. Solar gain during the day (global radiation × absorptivity 0.82 × 12 h) is a credit — in high summer it can drop the heat demand close to zero. A night cover reduces both evaporation (−85 %) and radiation loss (−90 %).

Basis: the applicable national standard

What do the applicable standards require regarding Outdoor-pool heat-up?

the national pool-operators association guideline R 60.03 on heating public outdoor pools: heat-up phase in April over 30 days, raising the set-point from 10 to 22 °C; slow heat-up (45 days) or solar absorbers as a pre-heat stage save energy. For 2,508 m³ of water × 12 K × 1.16 kWh/(m³·K) = 34,928 kWh — spread over 30 days that is 1,164 kWh/d of extra load. Recommendation: heat up via a pool heat pump on a warm source (backwash water already at 15 °C before season start) instead of a gas peak boiler. A pool cover shortens the time (solar gain by day, loss reduction by night).

Basis: the applicable national standard.03

What do the applicable standards require regarding Energy management of public pools?

the pool operating guideline fixes the order for refurbishments: 1) reduce losses (envelope, pool cover, insulate the surge tank, ventilation heat recovery), 2) recover heat (heat recovery, waste-water heat, filter backwash as a heat-pump source), 3) generate efficiently (heat pump > CHP > gas). This hierarchy is decisive for public grant applications: funders check whether losses were reduced before the generation investment. Concretely: insulate the surge tank, add an outdoor-pool night cover and service the ventilation heat recovery before or together with the heat-pump installation.

Basis: the applicable national standard.10